How to calculate the exact water loss in cooling tower? I need with reference and proper formula.

Using percentages are normal practice but i need exact calculations.

user-image
Question added by Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL
Date Posted: 2014/04/30

sorry thes is not in my specialty

Salman Ali Ammar
by Salman Ali Ammar , MEP Coordinator , Al Fara'a General Contracting

Actually according to my experience, every manufacturer provides the estimated evoparation loss according to his own selected model.

Mohammed Abrar Ali
by Mohammed Abrar Ali , Mechanical Engineer , Toor construction company

Very easy to calculate water evaporation loss, Here is an example.

Ex: If the water flow rate is30 GPM

Sol. W.E.L (m3/hr) =0.00085 x1.8 x water circulation rate (m3/hr) x Delta T (difference in temp)

                                                 (1 gpm =0.003785 m3/min )

                                                 (1 m3/hr =1000 lit/hr )

           (water circulation rate (30 gpm) =30 x0.003785 x60 (m3/hr) =6.813 m3/hr)

  Now, insert in above formula

                       =0.00085 x1.8 x6.813 m3/ hr x (35 c -31 c) 

                       =0.047 m3/hr is the water evaporation loss

Hope this example will help you.